ποσότητα:
Line Rated Current: 100 A
Number of Poles: 3P
protected poles description: 3t
Control Type: Toggle
breaking capacity code: G
breaking capacity:
65 kA 240 V AC 50/60 Hz UL 489
35 kA 480 V AC 50/60 Hz UL 489
18 kA 600 V AC 50/60 Hz UL 489
20 kA 250 V DC UL 489
20 kA 500 V DC UL 489
[Ue] rated operational voltage: 690 V AC 50/60 Hz IEC 60947-3
Συχνότητα δικτύου: 50/60 Hz
[Ics] rated service breaking capacity:
65 kA 220/240 V AC 50/60 Hz IEC 60947-2
35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2
18 kA 500/525 V AC 50/60 Hz IEC 60947-2
20 kA 250 V DC IEC 60947-2
20 kA 500 V DC IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV IEC 60947-2
trip unit technology: Thermal-magnetic
magnetic tripping current: 1700 A
magnetic hold current: 900 A
continuous current rating: 80 %
[Ui] rated insulation voltage: 750 V IEC 60947-2
utilisation category: Category A
AWG gauge
AWG 14…AWG 3/0 aluminium/copper terminal
local signalling
Switched off (OFF) 1 trip indicator green)
mounting mode: Unit mount lug)
Mounting Support: Lug
electrical connection: Lugs line Lugs load
terminal identifier: AL150HD
tightening torque:
44.25 lbf.in (5 N.m) 0.00…0.01 in² (2.5…6 mm²) (AWG 14…AWG 10)
123.91 lbf.in (14 N.m) 0.02…0.15 in² (10…95 mm²) (AWG 8…AWG 3/0)
number of slots”
2 auxiliary switch OF plug-in)
1 alarm switch SD plug-in)
1 overcurrent trip switch SDE plug-in)
1 voltage release MN or MX plug-in)
Power wire stripping length: 0.63 in (16 mm)
Color: Black
Height: 6.42 in (163 mm)
Width: 4.09 in (104 mm)
Depth: 3.39 in (86 mm)
Net Weight: 4.85 lb(US) (2.2 kg)
communication interface: Modbus
Κατάσταση: .